Atec T-R-50A-3PH User Manual

Browse online or download User Manual for Equipment Atec T-R-50A-3PH. Atec T-R-50A-3PH User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
50A-3PH Current Injection System
T&R Test Equipment is a market leader in the field of current
injection equipment. The range includes secondary injection
units with 50A output capability up to 6000A primary injection
systems. All have true RMS metering, a flexible timing
system, and an easy to understand user interface.
The 50A-3PH is a three phase injection system providing
commissioning and maintenance engineers with a flexible
system for testing protective systems. It has an easy to
understand panel layout and a simple user interface. The
status of every function can be seen at a glance, and there
are no complex menus to navigate.
The unit has a range of outputs allowing injection of currents
as low as a few mA and as high as 50A. Voltages up to 18V
are available on the main outputs. Three true RMS metering
ranges are provided, allowing the full scale of the meter and
trip level to be set independently of the selected output.
Industry standard safety connectors are used on all inputs
and outputs for convenience, reliability and safety.
The 50A-3PH is comprehensively protected by overcurrent,
duty cycle and thermal trips, and keeps the user fully
informed of any trip condition. Auxiliary outputs and inputs
are fuse protected.
An auxiliary metering input is provided and can measure
voltage, current, frequency, and the phase between any of
the current outputs and an external voltage or current.
The timing system is very flexible without compromising ease
of use, allowing trip times, reset times and reclose times to be
quickly measured to a high degree of accuracy. Two
independently isolated contact inputs are provided, and the
timing system may also be used as a stand-alone timer.
The 50A-3ph can be used to test many types of single and
three phase secondary protection including:
Over and under current
relays
IDMT relays
Auto-reclosers
Time delay relays
Earth fault relays
Miniature circuit breakers
Power relays
Tripping relays
Thermal relays
The back-lit display on the 50A-3PH is bright and
clear with a wide viewing angle. The results of a test
can be seen here as they appear on the display
Features
Clear and simple user interface
3 phase current output
0-50A per phase output current
True RMS digital metering
Memory ammeter
Multi-function timing system
Auxiliary metering input
Large back-lit liquid crystal display
Thermal and over-current protection
Compact and portable
220V 3φ or 400V 3φ supply options*
115V-440V 3 wire supply with
optional supply transformer
*See supply requirements overleaf
11
Page view 0
1 2

Summary of Contents

Page 1 - Current Injection System

50A-3PH Current Injection System T&R Test Equipment is a market leader in the field of current injection equipment. The range includes secondary

Page 2 - 50A-3PH Specification

Main Output The main output on the unit has two taps, allowing the selection of output voltages up to 18V and output currents up to 50A. Range

Comments to this Manuals

No comments